GUANYA WATER SOLUTION has prepared a seawater-cooling design for a site in Peru. The design flow is 5 m³/h. The design duty is to cool seawater from 20 °C to 5 °C and deliver a stable 5 °C stream after filtration. This is process cooling of seawater, not desalination. The site and client names are withheld.
This page is not GUANYA’s published design notes on seawater desalination for data-center cooling-tower makeup. Those pages remain separate, and this Peru duty should not be read as that application.
Country: Peru | Duty: Seawater process cooling | Design flow: 5 m³/h, 20 °C to 5 °C
The problem
A site in Peru needed to cool a seawater stream for a process duty, not to produce drinking water and not to treat seawater for data-center or cooling-tower makeup. The design duty is 5 m³/h, cooling the seawater from 20 °C to 5 °C, with materials chosen for seawater corrosion.
How the scheme solves it
GUANYA prepared a seawater-cooling treatment scheme, not a desalination plant. As shown on the process drawing, seawater is taken from a storage tank by an inlet pump at 5 m³/h and 20 °C, passes a self-cleaning filter, and is cooled in a freezing unit (marked 0 °C to −40 °C on the drawing) before an insulated water tank. A transfer pump and a precision filter deliver 5 m³/h at 5 °C to the terminal process use. An overflow outlet and a pump control box are included on the drawing. The design uses a corrosion-protected chiller and a titanium-tube heat exchanger. This scheme is distinct from GUANYA’s Peru acid-mine-drainage notes and from any data-center SWRO cooling notes. Equipment is factory-assembled and factory-tested; time to first cooled water depends on seawater supply, power and site hook-up.
Design drawings

Design basis
| Item | Design-basis value |
|---|---|
| Country / setting | Peru (site identity withheld) |
| Design flow | 5 m³/h of seawater |
| Design temperature change | Cooling from 20 °C to a 5 °C delivery temperature |
| Design cooling capacity | 105 kW, matched in the scheme to the 5 m³/h, 20 °C to 5 °C load |
| Design electrical input | 43 kW (nameplate / design figure, not a measured operating result) |
| Main equipment (design) | Air-cooled, corrosion-protected chiller; titanium-tube heat exchanger; insulated circulating seawater tank; automatic level make-up and temperature start–stop |
| Setpoint range (design) | 0–40 °C adjustable; the specified delivery temperature in this scheme is 5 °C |
| Seawater-wetted materials (design) | Corrosion-protected chiller, titanium-tube exchanger and a polymer tank selected for chloride service |
In the proposed control sequence, the tank is filled to a set level, the chiller starts when the tank temperature is above 5 °C, and it stops when the tank reaches 5 °C, holding the delivery flow at the design 5 m³/h. After heat exchange, the cooled seawater is described as passing a precision filter before the use point. These are design descriptions, not operating logs.
Related reading
- Seawater desalination for data-center cooling-tower makeup (a different duty: SWRO for makeup water, not this Peru seawater-cooling design)
- Acid mine drainage treatment in the Andes, 2.5 m³/h (a different Peru duty)
Frequently Asked Questions
Is this a desalination plant?
No. The design cools seawater from 20 °C to 5 °C at 5 m³/h. It does not produce fresh water by reverse osmosis.
Is this the same as GUANYA’s data-center cooling-tower SWRO notes?
No. Those notes concern seawater desalination for cooling-tower makeup. This page is a direct seawater-cooling duty in Peru and should not be combined with them.