GUANYA WATER SOLUTION has prepared a seawater-cooling design for a site in Peru. The design flow is 5 m³/h. The design duty is to cool seawater from 20 °C to 5 °C and deliver a stable 5 °C stream after filtration. This is process cooling of seawater, not desalination. The work is at design and quotation stage. The equipment has not been manufactured or commissioned by GUANYA, and this note is not an operating or shipped-plant reference. The site and client names are withheld.
This page is not GUANYA’s published design notes on seawater desalination for data-center cooling-tower makeup. Those pages remain separate, and this Peru duty should not be read as that application.
Status: Design proposal and quotation | Country: Peru | Duty: Seawater process cooling | Design flow: 5 m³/h, 20 °C to 5 °C
Design basis (proposal stage, not measured operation)
| Item | Design-basis value |
|---|---|
| Country / setting | Peru (site identity withheld) |
| Design flow | 5 m³/h of seawater |
| Design temperature change | Cooling from 20 °C to a 5 °C delivery temperature |
| Design cooling capacity | 105 kW, matched in the scheme to the 5 m³/h, 20 °C to 5 °C load |
| Design electrical input | 43 kW (nameplate / design figure, not a measured operating result) |
| Main equipment (design) | Air-cooled, corrosion-protected chiller; titanium-tube heat exchanger; insulated circulating seawater tank; automatic level make-up and temperature start–stop |
| Setpoint range (design) | 0–40 °C adjustable; the specified delivery temperature in this scheme is 5 °C |
| Seawater-wetted materials (design) | Corrosion-protected chiller, titanium-tube exchanger and a polymer tank selected for chloride service |
| Status | Design and quotation — not shipped, not commissioned |
In the proposed control sequence, the tank is filled to a set level, the chiller starts when the tank temperature is above 5 °C, and it stops when the tank reaches 5 °C, holding the delivery flow at the design 5 m³/h. After heat exchange, the cooled seawater is described as passing a precision filter before the use point. These are design descriptions, not operating logs.
What this page is not
It is not a shipped or operating plant, and it is not a seawater reverse-osmosis or drinking-water plant. It is not a data-center cooling-tower makeup desalination case. Hook-up time depends on site piping, power and commissioning.
Related reading
- Seawater desalination for data-center cooling-tower makeup (a different duty: SWRO for makeup water, not this Peru seawater-cooling design)
- Acid mine drainage treatment in the Andes, 2.5 m³/h — design and quotation (a different Peru duty)
Frequently Asked Questions
Has this Peru seawater-cooling system been shipped?
No. The status is design and quotation. The equipment has not been manufactured or commissioned by GUANYA.
Is this a desalination plant?
No. The design cools seawater from 20 °C to 5 °C at 5 m³/h. It does not produce fresh water by reverse osmosis.
Is this the same as GUANYA’s data-center cooling-tower SWRO notes?
No. Those notes concern seawater desalination for cooling-tower makeup. This page is a direct seawater-cooling duty in Peru and should not be combined with them.